Sealing around windows, and when the frame seal is behind the damp
Which silicone goes round a window outside, how deep it goes for each size of gap, when a gap is too wide for sealant at all, and how to tell whether the frame bead is even where the water is getting in.
By The Damp GuyLast updated
The short version
Outside, use a low modulus, neutral cure silicone classed for facades. Measure the gap before you buy anything. Between 5 and 10 mm is a sealant job, with foam backer rod behind it once the gap passes 6 mm so the bead only grips the two sides. Over 10 mm on an ordinary window is wider than the new-home warranty providers allow, and that is a fitting problem before it is a sealant one. And if water is coming in, check where the damp sits before blaming the bead, because the bead is only one of the ways rain gets through a wall at a window.
Which sealant goes round a window outside
Read the cartridge, not the name on the front of it.
The joint between a window frame and the wall moves, which is why every window silicone carries a movement rating. The sealant has to stretch without letting go. That is what low modulus means: it takes little force to stretch. Neutral cure is the other half, and it is about what the sealant gives off while it sets.
The standard for this job is BS EN 15651-1, which covers sealants for outside wall joints and window and door perimeter joints. A cartridge that meets it carries a code. F is facade. EXT and INT mean outside and inside. LM is low modulus. The number in front, as in 25LM, is how far it can move, 25%. CC means it is rated for cold climates, down to -30 C once cured. So the line you want on the back of the tube reads something like F-EXT-INT 25LM.
The name on the front is not enough, and one product shows why. Everbuild's External Frame Sealant is an acrylic. Its own data sheet lists it for outside work on timber and metal frames, for inside work only on PVCu, and says in as many words not to use it outside around PVCu. Its movement is rated at 12.5%, half a 25LM silicone's. Fine on a painted timber frame, and the sheet recommends painting over it outside. Wrong on a uPVC one. The longer argument is on caulk, acrylic and silicone, and where each one goes.
The silicone to keep away from brick, render and concrete is acetoxy cure, the one that smells of vinegar while it sets. It releases acetic acid, and makers advise against it on cement-based surfaces because it will not bond to them well enough. One last trap: if the sill is natural stone, check the sheet before you start, because some silicones stain marble and granite.
Measure the gap, then the table tells you the rest
Gap limits from the warranty providers, depths from the makers' own data sheets.

| The gap | Sealant depth | What goes behind it | Nozzle |
|---|---|---|---|
| Under 5 mm | Too narrow to fill. Every data sheet read sets a 5 or 6 mm minimum width | None. Run a fillet over the joint instead, at least 6 mm onto the frame and 10 mm onto brick or render | The angled tip, which runs a bead into a corner |
| 5 to 6 mm | At least 5 to 6 mm | A backing strip once the gap passes 5 mm, so the bead is not stuck to the back | 5 or 6 mm round |
| 8 mm | 6 mm | Closed-cell foam backer rod, about 10 mm across | 8 mm round |
| 10 mm | 6 mm | Closed-cell foam backer rod, about 12.5 mm across | 10 mm round |
| Over 10 mm | Half the width, so 20 mm wide is 10 mm deep | Backer rod, but on a window under 3 m wide this is past the 10 mm both warranty providers allow. That is a fitting problem first | Wider than any of the four round nozzles |
Gap limits, backing and fillet widths: LABC Warranty (May 2025) and Premier Guarantee (March 2025). Depths and minimum widths: the Everbuild Everflex 450, Soudal Silirub LMN and Geocel LMN data sheets. Rod sizes are worked from Sika's rule that the rod should be about 25% wider than the joint. Nozzle sizes are the round ones in the set further down, matched to the joint as Soudal advises. All read 6 October 2026.
The depth column decides whether the bead lasts. A bead stuck to both sides of the joint and to the back of it as well loses the flexibility the joint needs. That is three-sided adhesion. Closed-cell foam backer rod stops it. It holds the sealant at the right depth and the sealant does not bond to it, so the bead grips the frame and the wall and nothing else. Geocel's sheet gives exactly that as the reason to use it.
The sources disagree in two places, and both are worth knowing. On the narrow end, one sheet says 5 mm minimum and two say 6. On the wide end the gap is much bigger. The products will fill 30 to 50 mm. The warranty providers cap the gap round an opening under 3 m at 10 mm, and at 15 mm above that. A tube that can fill a 25 mm gap does not make a 25 mm gap right. LABC's note says a gap that wide pushes the sealant lines beyond acceptable limits just to cover the backing, and it is clear that a cover trim is not a weather seal unless it has been tested as one.
For laying the bead itself, taping, tooling and getting a neat line, there's a page on how to apply silicone sealant.
When the frame seal is the damp, and when it is not
A cracked bead is easy to see, which is why it gets blamed for water that came in somewhere else.
Approved Document C asks two things of the joint between a wall and a window frame. It should stop rain getting inside, and it should not let water reach any part of the building that water would damage. A failed bead breaks the first. That's real, and it is one of the defects behind penetrating damp: damp that arrives sideways through the wall from outside, and follows the rain.
But the same document does not trust the bead alone. It calls for damp-proof courses to turn water outward at a lintel, and under sills and at reveals wherever those joints do not form a complete barrier. In the most exposed parts of the country it wants the frame set back behind the outer brickwork in a checked rebate. So there are layers, and a wet patch inside can come through any one of them.
Where the damp sits is the first clue. At the head of the window, the lintel and the cavity tray above it are suspects before the bead is. Under the sill, look at the sill itself and how it is sealed at its ends. Down the sides of the reveal, the perimeter bead and the pointing beside it come into the frame. On uPVC, the glazing gaskets and the drainage holes in the frame are separate routes again. Rain penetration shows up as damp patches after heavy rain, around openings, and the Scottish building standards are honest that the route can be hard to pin down.
The usual way to narrow it is a hose, used in stages. Start low, wet one part of the outside at a time, work upward, and wait a few minutes between stages. When the water appears inside, the last place you wetted is your lead. Water running down the inside of the glass on a cold morning is a different thing altogether, and condensation on the glass has its own page.
This site can tell you what each pattern usually points to. It cannot tell you what is happening in your building. If the patch is at the head, or it is still wet after you have resealed, the next step is someone who can see it, and who you ask to look at it matters.
Doing it: the old bead, the weather and the cure
Most beads that fail early were put on over something, or on the wrong day.
The old bead comes out first, all of it. New silicone won't bond to cured silicone, and getting old silicone off is a job of its own. Then the joint wants to be clean, dry, sound and free from frost.
Pick the day. Soudal's window silicone goes on between 5 C and 35 C, and Soudal says plainly that sealant will not stick to a damp surface, so do not seal after rain or with storms forecast.
Seal inside and out. LABC wants the perimeter joint sealed continuously on both faces, and a seal between the sill and the frame with a barrier at the ends of the sill. Shape the outside bead so it sheds water. One maker's sheet says the seal must not form a water trap, and a triangular fillet should be at least 12 mm across its face.
Then leave it. These silicones cure from the outside in at 1 to 2 mm a day, so a 6 mm deep bead takes three to six days to cure through. The skin forms in 5 to 25 minutes, which is why it feels done long before it is. The detail is on how long silicone takes to dry. If the last window leaves you half a cartridge, a screw-on cap that plugs the spout stops what is left from setting in it.
One exception. On a listed or older building, check what is there before you reach for a gun. One council's conservation guidance says lime mortar or burnt sand mastic is the traditional seal between frame and wall, and that modern mastics and foam fillers should be avoided because they can trap moisture.
About this resource
The gap limits come from LABC Warranty's note on gaps around external windows and doors, dated May 2025, and Premier Guarantee's of March 2025. Neither sells sealant. The depths, widths and temperatures come from the makers' own data sheets, and every maker sells the product its sheet describes. The building regulations are Approved Document C. Every source is linked at the foot of the page.
Nothing here is a survey or a diagnosis. This site does not survey, treat or quote for work.
Common questions
Can I use silicone sealant on windows?
Yes, outside as well as in, as long as it is the right silicone. You want a low modulus, neutral cure sealant classed for facades. On the cartridge that reads as EN 15651-1 with F-EXT-INT and a class like 25LM, meaning facade use, outside and inside, and 25% movement. Skip any silicone that smells of vinegar. That is acetoxy cure, and makers advise against it on concrete, plaster and blockwork because it will not bond well enough.
Which is better for sealing windows, silicone or caulk?
Outside on a uPVC frame, silicone. One maker's acrylic, sold as External Frame Sealant, says on its own data sheet not to use it outside around PVCu. It rates its movement at 12.5%, half what a 25LM silicone allows, and recommends painting over it outside to make it last. Acrylic has its place on timber and metal frames you are going to paint.
Will silicone sealant stick to uPVC?
Yes. The window frame silicones are made for it. One low modulus neutral silicone lists sealing between PVC, treated timber and metal profiles as its use, and another lists perimeter pointing around PVCu frames inside and out with no primer generally needed. What stops it sticking is the surface: old sealant, dirt, frost or a damp frame. Soudal is plain that sealant will not adhere to a damp surface, so do not seal straight after rain.
How do you stop windows from leaking in heavy rain?
Find where it gets in before you buy anything. Rain penetration shows up as damp patches after heavy rain, around window openings, and the Scottish building standards admit the route can be hard to pin down. A cracked bead round the frame is one route. A missing tray over the lintel, a sill that does not seal at its ends, a failed glazing gasket and blocked drainage holes are others. Wet the outside in stages, from the bottom up, and see which stage brings the water through.
Where should you not caulk around windows?
Don't fill a joint so the sealant sticks to the back of it as well as both sides. Makers say that three-sided bond takes away the flexibility the joint needs. Use backer rod or a backing strip. Don't leave a bead shaped so it holds water, either. One maker's data sheet says the seal must never form a water trap. And on a listed or older building with lime, council conservation guidance says modern mastics and foam fillers should be avoided as they can trap moisture.
Can I reseal a window myself?
Yes, if the gap is within what a bead can handle. Measure it first. Between 5 and 10 mm is sealant work with the right backing behind it. Past 10 mm on a normal-sized window is wider than the warranty providers allow, so the frame fitting is the real question. And if the damp inside sits at the head of the window rather than the sides, a new bead is unlikely to be the answer.
Sources (16)
- LABC Warranty, "Gaps around external windows and door frames, sealants and finishing trims" (MK-3299-1.00, May 2025), read 6 October 2026
- Premier Guarantee, "Gaps around windows, sealants and finishing trims" (7 March 2025), read 6 October 2026
- Everbuild (Sika), Everflex 450 Builders Silicone product data sheet, April 2018, read 6 October 2026
- Soudal, Silirub LMN technical data sheet (rev 5 March 2020), read 6 October 2026
- Geocel, LMN technical specification (September 2013), read 6 October 2026
- Everbuild (Sika), Everflex 500 Bath & Sanitary Silicone data sheet, read 6 October 2026
- Sika, Sika Backing Rod product data sheet (2015), read 6 October 2026
- Everbuild (Sika), External Frame Sealant product data sheet, March 2018, read 6 October 2026
- Soudal UK, "What do the abbreviations mean on a UKCA marking?", read 6 October 2026
- Soudal UK, "Sealing windows" how-to, read 6 October 2026
- Penosil, "Neutral vs acetoxy silicones", read 6 October 2026
- BSI Knowledge, BS EN 15651-1 catalogue entry, read 6 October 2026
- HM Government, Approved Document C (2004 edition incorporating 2010 and 2013 amendments), read 6 October 2026
- Scottish Government, Building Standards Technical Handbook 2022 (domestic), 3.10 Precipitation, read 6 October 2026
- BookaBuilderUK, "uPVC window leak: seals, drainage holes", read 6 October 2026
- North Yorkshire Council, Conservation and Design Guidance Note 3, "Window Repair and Replacement in Listed Buildings" (15 October 2020), read 6 October 2026